Water Cooled Chiller Compressor Replacement Method
The method of replacing the compressor of the water-cooled chiller is as follows: cut off the power first, and be sure to cut off the power of the unit before replacing the compressor of the water-cooled chiller. Otherwise there is a risk of electric shock. When removing the power supply of the compressor, it is necessary to mark each wire and the corresponding terminal, so as to restore the wiring after maintenance.
Refrigerant discharge: Open the high and low pressure side valves of the industrial chiller with the inner hexagon, and pay attention to the ventilation of the surrounding environment to prevent the operator from suffocating. The speed of releasing the refrigerant should not be too fast to prevent the operator from being frostbitten by the refrigerant. If possible, the refrigerant of the water-cooled chiller should be recycled instead of directly discharged to maintain the environment.
Remove the suction pipe and exhaust pipe: Before removing the suction pipe and exhaust pipe, make sure that the refrigerant of the water-cooled chiller in the system has been exhausted. Heat the welding port with gas welding, after the welding port solder melts, pull out the suction pipe and exhaust pipe. During the whole welding process, be sure to fill with nitrogen, the nitrogen pressure is 0.5±0.1kgf/cm2, to prevent the copper tube of the industrial chiller from oxidizing and producing oxide skin, and also pay attention to whether there are impurities on the inner wall of the copper tube. When welding, pay attention to control the flame direction and avoid casing and sponge. wires, etc.
We are a professional manufacturer of temperature control equipment, supporting customized services, please consult us for details!
Temperature Control Range: -150°C to +50°C
Dynamic Temperature Control Systems
Temperature Control Range: -120°C to +350°C
Temperature Control Range: -40°C to +100°C
Temperature Control Range: -85°C to +250°C
Temperature Control Range: -150°C to -10°C